There are numerous considerations which can influence the layout and configuration

of a switchboard. The modular concept of Modis 12 has been specifically designed to

offer the OEM customer with ultimate flexibility, allowing the design and build of

distribution systems to meet the exact power expectations and space limitations of

individual schemes up to 1250A.

Utilising the latest MCB, MCCB and fuse combination unit technology, Modis 12

offers an extensive range of incomers, busbars, interconnections, service centres,

MCB distribution boards, and ancillary devices which are easily assembled in a

variety of switchboard configurations, from simple Form 2 single section panels

through to complex Form 4 Type 2 multi section switchboards.

Modis 12 offers enclosures of 750mm wide and cableways of 250mm wide, with a

selectable modular height increasing in 152.4mm increments up to 8 modules

(1219.2mm high). This innovative system enables horizontal and/or vertical stacking

of selected device enclosures, all with a common depth of 200mm.

 

For further information about this product click on this link to download the Modis12 catalogue

Specification:-

Quality Certificate of Manufacturer: ISO9001

Country of Origin: England

Type of Product: L.V. Switchboard

Standards: BS EN 60439-1 BS EN 60529

EN 60439-1 EN 60529

IEC 60439-1 IEC 60529

Forms of Separation: Forms 2 and 4

IP Rating: External IP3X as standard. IP4X when doors fitted

Construction: Frame Structure 1.2mm gauge folded steel

Construction: Cover Plates 1.2mm screw fixed sheet steel

Construction: Internal Segregation Aluzinc perforated sheet steel or transparent polycarbonate sheet

Cabling Access: Front access cabling. Entry via gland plates facilitating either

top and/or bottom entry

Busbars: Material HDHC Copper

Busbars: Mounting 3 and 4-pole air insulated mounted in glass fibre reinforced

moulded supports

Busbars: Shielding Non-conductive rigid insulated barriers or rigid sheet steel barriers

Busbars: Maximum Current and Fault Withstand Ratings Up to 1250A: 50kA for 1s

Rated Operational Voltage: 400V AC

Power Frequency Withstand Voltage: 2500V

Paint Finish: Colour light grey RAL 7035 semi-gloss

Paint Depth: 40/60 microns

Paint Process: 4 stage process of chemical spray degreasing, iron

phosphate coating, automatic electro-static epoxy

polyester film application and curing in a high temperature

controlled oven

Testing Recommendations All Modis 12 switchboards are to be electrically and

mechanically inspected and tested throughout the assembly

process. Final testing and inspection must include a dielectric

test, in accordance with EN 60439-1 and an insulation

resistance megger test.